Model : ST-1520

Digital Earth Resistance Tester ST1520


For checking the insulation resistance between the grounding point and terminals, and between the terminals and the outer casing of emergency bells and automatic fire alarm equipment.


st-1520-1.jpg



If you have any questions, 

please feel free to contact us!

 Measuring ranges

 Earth resistance
 0-20Ω / 0-200Ω / 0-2000Ω
 Earth voltage
 0-200 Vac (40-500Hz)

 Accuracy

 Earth resistance
 ±(2%rdg+2dgt) or ±0.1Ω, which is greater
 Earth voltage
 ±(1%rdg+2dgt)

 Earth resistance resolution

 0-20Ω : 0.01Ω
 0-200Ω : 0.1Ω
 0-2000Ω : 1Ω

 Measuring system

 Earth Resistance by constant current inverter 820Hz approx. 2mA. 

 Display

 3½ digit (2000 counts)

 Open circuit indication

 LED will be unlit

 Low battery indication

 "B" symbol appears on the display

 Data hold indication

 "DH" symbol appears on the display

Over range indication

 "1"(MSD)

 Dimensions

 163(L) × 100(W) × 50(D)mm

 Weight (battery included)

 Approx. 480g

 Power source

 1.5V (AA) × 6

  • Capable of measuring earth resistance and earth voltage.
  • 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.
  • Auto power off function.
  • The timer operates automatically for about three to five minutes when the "PUSH BUTTON SWITCH" and "TIMER ON BUTTON" are pressed together. This will keep test "ON" for the duration of the timer.
  • Timer for test function (count 3-5 minutes).
  • Battery operated.
  • Data hold function.
  • Small and light weight.
  • Calibration performed with supplied test leads.